Determine boiler size based on the area and age of the dwelling

Here you can find the required boiler size (boiler performance) based on your annual oil consumption or annual gas consumption
If the annual oil / gas consumption is not known, you can find the required boiler size based on the area and age of the dwelling.

Based on the age of the house and the desired heated area, the required boiler size can be read in the table below. Estimated power for hot water and loss (2 kW) is included.
The table shows the required boiler performance both for a house that meets the building regulations requirements for insulation and for the older and poorly insulated house.

If an oil furnace is included in the installation, it can be used as a spare in particularly stressed situations. In this case, the boiler can be sub-dimensioned to e.g. 75% of the dimensioned heat loss (lower limit).

Heated living area

75% coverage of the dimensioned heat loss in homes built after 1985

Homes built after 1985

housing built before 1920

Boiler output (kW)

Boiler output (kW)

Boiler output (kW)

100

6

10

16

200

13

16

31

300

17

24

46

400

23

30

60

500

28

37

75

600

33

45

90

Source: Institute of Technology, Biofuel Boiler Installation Guide, October 2000