Determine boiler size based on the area and age of the dwelling
Here you can find the required boiler size (boiler performance) based on your annual oil consumption or annual gas consumption
If the annual oil / gas consumption is not known, you can find the required boiler size based on the area and age of the dwelling.
Based on the age of the house and the desired heated area, the required boiler size can be read in the table below. Estimated power for hot water and loss (2 kW) is included.
The table shows the required boiler performance both for a house that meets the building regulations requirements for insulation and for the older and poorly insulated house.
If an oil furnace is included in the installation, it can be used as a spare in particularly stressed situations. In this case, the boiler can be sub-dimensioned to e.g. 75% of the dimensioned heat loss (lower limit).
Heated living area
75% coverage of the dimensioned heat loss in homes built after 1985
Homes built after 1985
housing built before 1920
m²
Boiler output (kW)
Boiler output (kW)
Boiler output (kW)
100
6
10
16
200
13
16
31
300
17
24
46
400
23
30
60
500
28
37
75
600
33
45
90
Source: Institute of Technology, Biofuel Boiler Installation Guide, October 2000